Using Hall effect and open-loop measurement principle, after TRMS calculation, the measured current is converted into DC current or voltage output proportional to the primary current, and the current sensor can measure DC, AC, pulse and various irregular waveforms of current under the condition of electrical isolation. It has the characteristics of high accuracy, high linearity, high integration, small size, simple structure and long-term stability.

Description

Advantages

Parameters

Selection

Download


Elucidation: 1,Va 2,Iour 3,NC 4,0V(power ground) OFS, zero adjustment BAI, error adjustment GIN, amplitude adjustment


Remarks:

1.Incorrect wiring may cause damage to the sensor. After the sensor is powered on, when the measured current passes through the sensor window, the proportional voltage value can be measured at the output end.

2.The output amplitude of the sensor can be adjusted according to the user's needs.

3.Sensors with different rated input current and output voltage can be customized according to user requirements.


Electrical characteristics


Type

FS100 RST1

FS200 RST1

FS300 RST1

FS400 RST1

FS500 RST1

FS600 RST1

FS1000 RST1


lpN

Primary nominal input current

0~100

0~200

0~300

0~400

0~500

0~600

0~1000

A

lp

Measuring range ofprimary current

0~±150

0~±300

0~±450

0~±600

0~±750

0~±900

0~±1200

A

lout

Rated output voltage

4~20(±1%)

mA

RL

Load resistance

80~650

Q

Vo

Supply voltage

+20~+32(±5%)

V

lo

Current consumption

Ve=+24V                           30+Iour

mA

Va

Insulation voltage

5kV RMS /50Hz/1 min between primary and secondary side circuits


EL

Linearity

<1

%FS

lo

Zero offset current

TA=25℃                           4±0.1

mA

lom

Residual voltage

Ip→0                              <0.1

mA

lor

Offset current temperature drift

Ip=0 TA=-25~+85℃                <0.005

mA/℃

Tr

Response time

<150

ms

f

Frequency bandwidth(-3dB)

D0,20~6000

Hz

TA

Ambient operating temperature

-25~+85

Ts

Ambient storage temperature

-40~+100

RL

Load resistance

≥10K

Q

m

Quality (approx.)

248

g


Standard

SJ 20790-2000;JB/T 7490-2007



Classify Title Download

Need Any Help

Leave your contacts and our engineers will help you to find the solution you are looking for.

Contact us for further information

The content with * is required

Related Products

0

Let’s talk! We’ll provide the perfect solution for you!

Shanghai Freesor Sensor Technology Co. ,Ltd. was founded in 2005 by a number of overseas returnees with rich experience. It is a high-tech enterprise integrating design, research and development, production and sales.

Copyright © 2024 Shanghai Freesor Sensor Technology Co. ,Ltd.           Privacy Policy Powered by Bontop